Note: Above tables reference the voltage drop over distances. It was
determined by using selection criteria of Motor Properties Table. In
order to determine the voltagedrop, multiply the length by the data
above.
For Example: For a 5 HP and 460 V motor, P/N 701804 would be used. For a
distance of 200 feet, your voltage drop would be 200x.058=11.6 volts.
*Value is based on using single conductor table. |